Damage Prevention Solutions

Kentucky Specifications & Guidelines

Kentucky Transportation Cabinet

Standard Specifications for Road and Bridge Construction, Edition of 2019

716.03.05 Underground Warning Tape

"Install underground utility warning tape immediately above the circuit cables that are in duct or conduits. Bury the tape at a depth of 6 to 10 inches."

> Open Specification Document

834.33 Warning Tape

"Provide tape that is 6 inches wide and 7.0 mils (nominal) thick. Provide tape that has a minimum tensile strength of 600 pounds per 6 inch width and that is color-coded and impregnated with alkali and acid stable, lead-free, organic pigments that are suitable for direct burial. Use tape that is ultraviolet colorfast and non-distorting with no elongation. Use tape that includes black lettering and symbols on a gray background that conforms to the APWA-ULCC national color code for DOT. Provide tape that continuously reads, "CAUTION: ELECTRIC LINE BURIED BELOW" alternating with a “No Digging” symbol."

> Open Specification Document

Call Before You Dig

Kentucky 811

Call: 811 (Local) or 800-752-6007

Click: https://kentucky811.org/

Product Approvals

Copyright © 2024 Damage Prevention Solutions, LLC
Privacy Policy
3M Authorized ManufacturerMade in USA of US and Imported Parts